85 1/2
[2,172]
90 1/2
[2,300]
36 1/2
[929]
7 1/2
[192]
20 3/4
[529]
TRACED AND INSULATED
SUPPLY MUST BE HEAT
IMPORTANT
30°
1-1/4" IPS SUPPLY
UNION (INLET) TOP
SUPPLY SHOWN. SEE
STEP 2 OF
INSTALLATION
PROCEDURE IN THE
O&M MANUAL TO
CONVERT TO A
BOTTOM SUPPLY UNIT
POWER
CONNECTION
6 3/4
[171]
FLOOR LINE
ø9
[ø228]
3X ø3/8
[ø10]
ø8
[ø203]
NOTES:
1. DIMENSIONS IN BRACKETS ARE IN MILLIMETERS.
2. UNLESS OTHERWISE SPECIFIED ALL TOLERANCES TO BE +/- 1/4 INCH.
3. TO COMPLY WITH ANSI Z358.1-2009 FOR EMERGENCY EYE/FACE WASH AND SHOWER EQUIPMENT:
- UNIT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTABLE PLUMBING PRACTICES.
- EYE/FACE WASH SHALL BE POSITIONED WITH NOZZLES NOT LESS THEN 83.8 CM (33 IN.) AND NO GREATER THAN 114.3 CM (45 IN.)
FROM SURFACE ON WHICH USER STANDS AND 15.3 CM (6 IN.) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.
- SHOWER SHALL BE POSITIONED SO THAT SHOWER HEAD IS NOT LESS THAN 208.3 CM (82 IN.) NOR MORE THAN 243.8 CM (96 IN.)
FROM SURFACE ON WHICH USER STANDS.
- SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 50.8 CM (20 IN.) AT 152.4 CM (60 IN.) ABOVE SURFACE ON WHICH
USER STANDS, AND CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 40.6 CM (16 IN.) FROM ANY OBSTRUCTION.
(NOTES CONTINUED ON SHEET 2 0F 3.)
95 3/4
[2,431]
THERMOSTAT
NO LIFT
HEAT TRACE
TERMINATION
COUPLING
NO LIFT
POWER
CONNECTIONS
KEE KLAMP
APPROVED:
DRAWN:
PART NUMBER
DRAWING NO.
SCALE:
SHEET OF
REV
DRAWING TYPE: SIZE: A
BY:ECN NO.
PAGE
DATE:
DATE:
ECN:
REVISED PER
CHK'D.:
Haws Corporation - All Rights Reserved.
HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation.
C
R
MODEL(S)
1455 KLEPPE LANE
SPARKS, NEVADA 89431
(775) 359-4712 FAX (755) 359-7424
E-MAIL: HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM
THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.
SLS
7/17/08
15363A00
9
0002077032.D
8317CTFPC1D1
1:1
14
4140
HM
7 of 10
INSTALLATION
4888
2014
41 3/4
[1060]
SP158B FREEZE PROTECTION VALVE
(SEE NOTES ON SHEET 2 & 3 FOR
INSTALLATION INSTRUCTIONS.)
6 3/4
[171]
14"
[355]
NOTE: PULL ROD AND HANDLE NOT
ASSEMBLED. ORIENTATION OF HANDLE
MUST BE IN UP POSITION WHEN FULLY
CLOSED AND PULL ROD INSERTED IN
HOLE SHOWN.
VIEW ROTATED 180°
SEE
DETAIL A
DETAIL B
SEE MOUNTING
Comentarios a estos manuales